QuestionI live in north fla. I have had a irrigation well I insalled 10yrs ago I am 30ft.down witha well point I had a leak on the suction pipe check valve corrected the leak now I can't get more than 20 psi water pressure my pressure switch is on at 20 off at40 psi I have 3 zones I think I have a collpsed well? 2 new wells have been put in on both sides of me with in the last year.How do i clean out the well point? I thought maybe pressure washer down the well pipe? can you help me please thank you. tony
AnswerThanks for your question.
I doubt you've collapsed the well. A pump doesn't have enough suction to do that. To clean a point you need to apply pressure to the well. Instead of sucking water in through the point your forcing water out through it. This would help push a bit of the debris away from the well screen.
Truthfully, I think you probably still have a suction air leak. Well screens don't plug-up in a few days they slowly diminish in production over time. Recheck all of your connections. Try applying water pressure to the pump. Any suction leaks before the check valve will show.
Good luck, if you have further question feel free to ask.
Matt